DCM 200 Installation
Page 24
5.2.
Communications
5.3. Ethernet LAN TCP-IP:
The DCM 200 controller contains a 10 Base T, RJ45 Ethernet port with a Fixed IP address assigned by
the administrator. Additional parameters adjustable are Netmask, Gateway and Primary DNS. The
controller operates as an HTML micro-server for command & control using Microsoft Windows IE7 and
Mozilla’s Firefox internet browsers available on most computers.
Logged data is served as an XML file in response to an HTML request. This feature makes
configuration easy using common Ethernet network browsers already installed on most computers, and
easily supported by local IT departments.
5.4. USB Services
All DCM 200 controllers include a USB port which is used for unformatted datalogging extraction to a
USB “thumb drive”.
5.5. Data Logging
Each enabled input and output is logged by the controller as a user set interval from 1
to 1440 minutes.
The default rate for all data is 60 minutes with a 2400 sample log size. Range is 4 to 600
days. Default maximum is therefore ~40 days of information.
5.3. Control Configuration
5.3.1. Control Method
Relays 1 to 5 ON/OFF Controls
The distance between the “Turn ON” and “Turn OFF” setpoints, sets the deadband (hysteresis) response
of an ON/OFF relay, controlled by sensors A,B andC. Not applicable to relays controlled by volume
meters or contact set F.
Method Function Examples
Rising Setpoint
[Feed Down]
ON: Sensor > Turn ON Setpoint
OFF: Sensor < Turn OFF Setpoint
Acid Feed
Falling Setpoint
[Feed Up]
ON: Sensor < Turn ON Setpoint
OFF: Sensor > Turn OFF Setpoint
Oxidant Feed
Caustic Feed
Between Setpoints
[Not normally used in pools
and spas]
ON: Sensor < Turn ON Setpoint
& Sensor > Turn OFF Setpoint
OFF: Sensor > Turn ON Setpoint
Sensor < Turn OFF Setpoint
Blocking Controls or
Level Controls
Event Rising
[Not normally used in
Aquatic applications]
Rising Setpoint Operates only during
Timed Events
Caustic Feed or
Dechlorination
Event Falling
Falling Setpoint
Operates only during Timed Events
Oxidant alternate setpoint
Event Between
[Not normally used in
Aquatic applications]
Between Setpoints
Operates only during Timed Events
Blocking – sequencing
controls.