DCM 200 Installation
Page 20
3.
Calibrations
3.1. Single Point Calibrations, One-Point or Standardization
The pH and Temperature inputs A and C, have single point (Offset only) calibrations.
Input B is the ORP input and should never need field calibration. Calibration of contact set inputs “E and
F” is blocked.
3.2. Two Point Calibration
Two point calibration is limited to pH sensors.
Sensor OFFSET is adjusted so the sensor value matches the user’s calibration value.
Sensor GAIN is adjusted so that the sensor value matches the user’s calibration value. This is the
measured response for each engineering unit, and normally does not change for pH and Temperature
sensors used in aquatic applications.
The value of a sensor = Measured Level (mV) x GAIN + OFFSET.
This value may be modified by sensor compensation.
Compensation (Temperature, Rate-Volume, Corrosion Rate…) is applied after GAIN & OFFSET.
During calibration, users have the option to Reset to Factory, which resets the sensor GAIN & OFFSET
to default values.
If the calibration OFFSET or GAIN is outside fault limits, users are offered the option to OVERRIDE.
OFFSET or GAIN outside of the fault limits (typically indicates a sensor, cabling or driver fault).
OVEWRRIDE consists of submitting or pressing enter an additional time.
Users also have the option to manually enter OFFSET and GAIN by selecting Sensor then Configure in
the Browser interface. See the DCM200 Browser Manual for more information.
WATER METER F:
When Input F is configured as a volume (flow) meter, the user calibration value is Volume/contact for
contact head meters and ‘K’ factor (Pulses per unit volume [gallon]) for turbine and paddlewheel meters.
Reset to Factory
Newly installed firmware & reconfigured water meters are Reset to Factory Default calibrations when
controller Power is first turned on after install.
User selected Reset to Factory loads the GAIN, OFFSET set from the following table.
n
p
ut
Type
Gain
Offset
MAX
MIN
Calculated Value
100 0 None None
Manual Entry
1 0 0 0
pH
pH
ORP
0.017
-1
7
0
OFFSET
NA
OFFSET
NA
Temperature
Temp OFFSET OFFSET