
DCM 200 Installation
Page 23
4.5. Passwords Reset
Contact ProMinent Technical Department, at (412) 787 – 2484,
with the controller serial number to obtain a
reset password which resets all passwords to the factory defaults shown above.
Proof of controller ownership is understandably required.
ProMinent controllers have no backdoor or super user password.
If you forget the password, this is the only way to recover controller access.
5. Application Notes
5.1. Sensor Inputs & Control Outputs
The controller uses the letters ‘A’ thru ‘F’ to identify input sensors, like pH, ORP, and Temperature, Flow
Switch, Surge Tank Level, Recirculation water flow meter, and other Digital signals. The numbers 1 to 5
identify the three (3) AC power switching relays and two (2) DC outputs for enable, alarm or pump pulse
frequency use.
‘A’ to ‘C’ and ‘E’ to ‘F’ exist as terminal blocks where inputs are connected. Sensor input ‘D’ is ‘virtual’ and
used to calculate Ryznar’s and Langelier’s SI indexes.
Users can also change the default names of sensors, pumps and valves to more meaningful, site specific
names. For example, although you may name controller meter input “E” to “Flow Switch”, ‘E’ identifies
where the meter is connected and the letter “E” is used to represent the “Flow Switch” input in hardware
connections and data logging.
Most inputs may be used to control almost any output with some logical aquatic application exceptions.
Sensor
Fixed pH sensor input Support for all ProMinent pH sensors.
All controllers have one pH sensor input.
Sensor
Fixed ORP sensor input Support for all ProMinent ORP sensors.
All controllers have one ORP sensor input.
Sensor
Temperature Support for the ProMinent SGT 10mV/K temperature
Thermal compensation for the ‘A’ pH sensor.
Phantom or
Virtual Sensor D
Phantom sensor inputs
have no physical
connection and are used
for control and logging.
This is a calculated value for LSI/Ryznar’s scale and
corrosion indecies.
Sensor
Fixed digital input There are two digital inputs. Input E is always used as the
Sample flow switch.
Sensor
Fixed digital input Digital input ‘F’ can be configured as an additional flow
switch or interlock, remote enable/disable, float switch, or
square wave pulsing flow meter.
Relays
to
AC Line powered outputs
ON/OFF controls
Controller powered outputs switch 120 VAC pumps, valves
& solenoids ON/OFF. Log time ON. Relays are N.O. only.
Relays 2-5 are SPDT for motorized valves requiring power
OPEN & power CLOSE if needed. Outputs can alarm on
runtime per actuation and per day.
Relays 4 and 5
DC switching outputs
Pulsing or ON/OFF
controls
DC Alarm Contacts, remote enable, or Variable speed pulse
output feeds. Presets for popular ProMinent and other pump
ml/stroke and maximum rates.
Comentarios a estos manuales