DCM 200 Installation
Page 14
There is not a Sensor transmitter (preamplifier) available for the DCM 200. Sensors, may be not be
extended past the maximum available length of coaxial SN6 cable, 33 feet (10 meters). For applications
where the distance from the controller to the sensors exceeds 33 feet, consult your ProMinent distributor
for options available to you.
Verify that the shields on water meters are also spliced if meter cables are extended.
Ground signal cable shields at one end only to the internal frame lower bottom grounding screw.
1.11. Ethernet LAN Cabling
CAT5 LAN cabling is limited to a maximum of 300ft / 100m from controller to access hub.
Do not exceed this limit.
Controller Enclosure Wiring
If shipped with the controller pre-mounted to an acrylic back panel, the controller has already been
wired to the sensors you purchased with the controller. Unless requested otherwise, the controller
has also been equipped with a 120VAC power cord. Refer to sections below for proper wiring of
power, individual sensors and feeders.
To facilitate easier wiring connections, the enclosure lid can be “parked in the open position as shown
below.
1. Loosen enclosure lid’s captive screws.
2. Carefully pull lid straight out just a few inches to avoid unplugging ribbon cables and internal
connectors.
3. Raise lid straight up until tabs on the sides of the lid align with recessed parking slots on the
side of the rear enclosure section.
4. Push tabs into slots until they snap into place, supporting the lid in an upright orientation.